Domestic & Panel Wires


Single / Multicore Cables made of annealed electrolytic grade copper / aluminium conductor, PVC insulated and PVC sheathed confirming to IS 694:1990, BS 6500 or any other international or customer specific standard.
» Conductor - Annealed Bare Electrolytic grade copper / aluminium uniformly bunched (for stranded and flexible conductors).
» Insulation - Specially formulated high grade PVC Compound confirming to Type A of IS 5931:1984 capable of withstanding conductor temperature upto 700C. The insulation is resistant to moisture, oils, alkalies, grease etc. The insulation process is carried out on modern high speed extrusion lines with automatic diameter controllers, spark testers, tension controllers, and centricity controllers for uniform and accurate insulation.
» Sheathing : PVC compound type ST2 of IS 5831:1984.

The insulation and sheath can be of HR ,FR, FRLS PVC, FRHF (Flame Retardant Halogen Free) or ROHS PVC Compound depending upon the application.
Nominal Cross Sectional Area of Conductor Sq. MM Number of wires / Diameter (mm) Thickness of Insulation (Nominal) Overall Diameter Maximum (mm) Current Carrying Capacity in Conduit / Trunking (Amps) Resistance (Max) at 20°C (Ohms/Km)
0.75 10/0.30 0.6 2.8 8 26
1 14/0.30 0.7 3.2 13 18.1
1.5 22/0.30 0.7 3.4 16 12.1
2.5 36/0.30 0.7 4.2 20 7.41
4 56/0.30 0.8 4.8 26 4.95
6 84/0.30 0.8 5.6 36 3.3
10 140/0.30 1 6.8 51 1.91
16 226/0.30 1.2 8.2 57 1.21

OrientCab" Plain Copper Conductor, PVC Insulated and Sheathed 650/1100 V, Multicore Flexible Cables as per IS : 694/1990

OrientCab" Plain Copper Conductor, PVC Insulated and Sheathed 650/1100 V, Multicore Flexible Cables

Comparative Properties Of Orientcab Wires With Different Insulation Materials
Feature Normal PVC FR PVC (Flame Retardant) FRLS PVC (Flame Retardant Low Smoke) ZHFR (Zero Halogen Flame Retardant)
Insulation Material PVC Special PVC Special PVC Special Polymer
Insulation Properties Normal Good Good Very Good
Temperature Rating 70°C 70°C 70°C 85°C
Flame Retardant Properties Good Very Good Very Good Excellent
Safety During Burning Average Very Good Very Good Excellent
Requirement of Oxygen to Catch Fire (% in air) >21 >30 >30 >35
Colors:- Red, Yellow, Blue, Black, White, Green Or Grey